Artificial intelligence (AI) policy: ASHRAE prohibits the entry of content from any ASHRAE publication or related ASHRAE intellectual property (IP) into any AI tool, including but not limited to ChatGPT. Additionally, creating derivative works of ASHRAE IP using AI is also prohibited without express written permission from ASHRAE.

Close
logoShaping Tomorrow’s Global Built Environment Today

Addenda to Standard 90.1-1999

Share This

Standard 90.1-1999, Energy Standard for Buildings Except Low-Rise Residential Buildings

NOTE: All documents linked from this page are in pdf_icon.png PDF-format.

(These descriptions may not be complete and are provided for information only.)

pdf_icon.png Addendum a (Clarification to 5.2.1.2, Substantial Contact.)

pdf_icon.png Addendum d (Clarifies what F-factors should be used for trade-offs in the calculation procedures for slab-on-grade insulation in 5.3.1.5, Slab-on-Grade Floor Insulation. Appendix A, Section A6.)

pdf_icon.png Addendum e (Clarifies that the calculation procedures in Section A9 can also be used for determining heat capacity of assemblies not covered in Tables A6 and A7.)

pdf_icon.png Addendum f (Revises Appendix B to change the unheated slab-on-grade floor criteria for residential spaces.)

pdf_icon.png Addendum g (Revises Appendix B to change the heated slab-on-grade floor values in Tables 19 through 26.)

pdf_icon.png Addendum j (Changes to 6.2.1, Mechanical Equipment Efficiency, and corresponding Tables 6.2.1C, H, I & J.)

pdf_icon.png Addendum k (Exceptions to 6.2.3.1.1, General, have been reworded for clarity and consistency.)

pdf_icon.png Addendum n (Change to the Exceptions to 6.2.3.2.4, Shutoff Damper Controls relates to gravity dampers and makes the statement consistent with the requirements of 6.1.3 (n), Simplified Approach Option for HVAC Systems.)

pdf_icon.png Addendum o (Change to 6.2.3.2.5, Zone Isolation, clarifies how zones may be grouped and removes the detailed performance requirements.)

pdf_icon.png Addendum q (Deletes 6.2.3.5, Enclosed Parking Garage Ventilation, in its entirety.)

pdf_icon.png Addendum r (Revises Exception to 6.3.1 (b) with regard to economizers.)

pdf_icon.png Addendum s (Exception to 6.3.1.4, Economizer Heating System Impact, was added to ensure that code officials would allow economizer operation where reheat was allowed.)

pdf_icon.png Addendum t (Change to 6.2.5.3.1, General, and 6.2.5.3.2, Air System Balancing, relates to system balancing and removes the exception to 6.2.5.3.1.)

pdf_icon.png Addendum u (Change to Table 6.2.1B, Electrically Operated Unitary and Applied Heat Pumps-Minimum Efficiency Requirements, adds the heat pump minimum efficiency ratings using the ISO procedure that are equivalent to the current requirements.)

pdf_icon.png Addendum v (In 9.2.1.1, Automatic Lighting Shutoff, the term 'occupant intervention' is vague and needed clarification.)

pdf_icon.png Addendum w (Change to 9.3.1.2, Space-by-Space Method of Calculating Interior Lighting Power Allowance, clarifies the intended use of this additional interior lighting allowance.)

pdf_icon.png Addendum y (Clarifies the definition of 'General Low Bay' and 'General High Bay' under the heading of Industrial Buildings, Table 9.3.1.2, Lighting Power Densities Using the Space-by-Space Method.)

pdf_icon.png Addendum z (Change to 9.3.2, Exterior Building Lighting Power, and Table 9.3.2, Lighting Power Limits for Building Exteriors, clarifies the language and intent of exterior building lighting power.)

pdf_icon.png Addendum aa (Change to 8.2.1.1, Feeders, and 8.2.1.2, Branch Circuits, specifies that connection load is not always the sizing method used in electrical design.)

pdf_icon.png Addendum ab (Change to 9.3, Prescriptive Path, and Table 9.3.1.2, Space-by-Space Method of Calculating Interior Lighting Power Allowance, clarifies that the additional power allowances apply to any lighted area that meets the criteria.)

pdf_icon.png Addendum ac (Change to 7.2.1, Sizing of Systems, provides additional wording to the designer for more flexibility in determining the load of the system.)

pdf_icon.png Addendum ad (Numerous changes including Tables 6.2.1A, 6.2.1B, 6.2.4.2B, and 6.1.3; 6.2.3.1, 6.2.4.1, 6.2.5.1 & 6.2.5.2.)

pdf_icon.png Addendum af (Changes to 4.1.2.2, strengthens the standard, eliminates the possibility of loopholes.)

pdf_icon.png Addendum ag (Changes to 5.2.2.1, 5.2.2.2, A8, Tables A-17, A-17 and A-19. Revise U-factor requirements for glazed wall systems in vertical fenestration to require compliance with NFRA certification programs.)

pdf_icon.png Addendum ah (Change to 9.3.1.1, allow building area lighting power allowance method to be used for all buildings.)

pdf_icon.png Addendum ai (Change to 9.3.1.1, adding footnote to Table 9.3.1.1 to indicate specific building types apply.)

pdf_icon.png Addendum ak (Appendix B, Tables B-1 to B-26 (SI only): Revises all U-factors in SI edition to be consistent with the IP edition.)

pdf_icon.png Addendum al (In Section 3 modifies the definition of pump system energy demand. Also, change to 6.3.2.1, 'mechanical refrigeration' to 'mechanical cooling', and 6.2.5.3, deleted certain requirements for system balancing.)

pdf_icon.png Addendum am (Changes to subsections of 4.1 and exceptions, rewritten version of Section 4 makes clear the different treatments given to additions and alterations to existing buildings.)

pdf_icon.png Addendum an (Change to 11.4.2, coordinates subsection 11.4.2 with 4.1.2.1 and 4.1.2.2.)

pdf_icon.png Addendum ao (Changes to the entire Section 5. No changes to the requirements. The revision simply restructures to make it easier to read and use.)

pdf_icon.png Addendum ap (Wording change to 11.4.3(e) and (f), this clarifies the rules for air and water economizers for budget building design.)

Close